Karl Klein Ventilatorenbau GmbH - Industrieventilatoren

Product search

Hint

Please note, that your operating point ideally should be selected in the middle of the fan characteristic curve.

If, for whatever reason, you have to deviate from this rule, the operating point must not be in the absolute marginal areas of the characteristic. The efficiency of the fan is too poor in the far right area and the characteristic curve is also inconsistent in the far left area, where flow may stall. In the case of ATEX fans, the operating point must be in the continuous range of characteristics, i.e. not too far in the left area.

Note: The fan characteristics shown here serve as reference values ​​for a quick pre-selection / configuration of a fan. For technical reasons, the characteristic curves shown here in the marginal areas (in which the fan should not be operated) may be subject to tolerance, they may differ slightly from our official fan data sheets.

Use our standard or advanced search to find the product you're looking for.

by power

m³/h
Pa

or by product type

or by type of fan

Advanced Search

m³/h
Pa
%
In "Operating Optimum" mode, other parameters cannot be entered
Hz
1/min
1/min
kg/m³
Volume Flow
Δp s
Δp t
Rated Power
Explosion Protection
Direct Current
Adjustable Frequency
ρ
Sound Pressure
ErP
DSV2 250-2-75
506
m³/h
830
Pa
991
Pa
-
-
0.37
kW
II 2D Ex h IIIC T135°C Db
-
+
1.2
kg/m³
72
dB(A)
-
DSV2 250-4-60
408
m³/h
838
Pa
980
Pa
-
-
0.37
kW
II 2D Ex h IIIB T4 Db
-
+
1.2
kg/m³
78
dB(A)
-
DSV2 250-4-60
392
m³/h
796
Pa
926
Pa
-
-
0.37
kW
-
-
+
1.2
kg/m³
77
dB(A)
-
DSV2 280-2-85
1087
m³/h
892
Pa
955
Pa
-
-
0.55
kW
-
-
+
1.2
kg/m³
84
dB(A)
2021
DSV2 280-2-85
1137
m³/h
899
Pa
967
Pa
-
-
0.55
kW
II 2G Ex h IIB T4 Gb
-
+
1.2
kg/m³
85
dB(A)
2021
DSV2 280-4-67
927
m³/h
1041
Pa
1107
Pa
-
-
0.55
kW
II 2D Ex h T125°C Db
-
-
1.2
kg/m³
75
dB(A)
2021
DSV2 315-2-95
1636
m³/h
1154
Pa
1273
Pa
-
-
1.1
kW
II 2D Ex h IIIC T135°C Db
-
+
1.2
kg/m³
76
dB(A)
2013
DSV2 355-4-85
1836
m³/h
1655
Pa
1874
Pa
-
-
1.5
kW
II 2D Ex h T125°C Db
-
-
1.2
kg/m³
90
dB(A)
2021
DSV2 400-2-118
3460
m³/h
1946
Pa
2474
Pa
-
-
4
kW
II 2D Ex h T125°C Db
-
-
1.2
kg/m³
80
dB(A)
2013
DSV2 400-4-95
3350
m³/h
1937
Pa
2604
Pa
-
-
3
kW
II 2G Ex h IIB T4 Gb
-
+
1.2
kg/m³
92
dB(A)
2021
DSV2 450-4-106
3585
m³/h
2678
Pa
2916
Pa
-
-
5.5
kW
-
-
+
1.2
kg/m³
90
dB(A)
DSV2 450-4-106
5101
m³/h
2409
Pa
2703
Pa
-
-
5.5
kW
II 2D Ex h T125°C Db
-
-
1.2
kg/m³
90
dB(A)
DSV4 250-2-75
224
m³/h
197
Pa
229
Pa
-
-
0.12
kW
II 2D Ex h IIIC T135°C Db
-
+
1.2
kg/m³
56
dB(A)
DSV4 250-4-60
200
m³/h
200
Pa
235
Pa
-
-
0.12
kW
II 2D Ex h IIIC T135°C Db
-
+
1.2
kg/m³
62
dB(A)
DSV4 315-4-75
643
m³/h
294
Pa
314
Pa
-
-
0.12
kW
II 2D Ex h IIIC T4 Db
-
-
1.2
kg/m³
63
dB(A)
DSV4 355-4-85
882
m³/h
384
Pa
408
Pa
-
-
0.25
kW
II 2D Ex h T125°C Db
-
-
1.2
kg/m³
65
dB(A)
2015
DSV4 560-4-132
3848
m³/h
1076
Pa
1172
Pa
-
-
2.2
kW
II 2GD Ex h T4
-
+
1.2
kg/m³
82
dB(A)
2021
Anfrageformular

Sie haben in unseren Produkten nicht das passende für Sie gefunden? Gerne machen wir Ihnen auch individuelle Angebote. Mit unserem Anfrageformular helfen Sie uns, ihre Anfrage schneller und besser zu bearbeiten.